Place of Origin: Henan, China

Brand Name: Zhenglan Cable

Certification: 3C; ISO 9001:2015, ISO 14001:2005, OHSAS 18001:2007

Model Number: Nominal Area:400mm2 AAC Overhead Bare Conductor Wire

Payment & Shipping Terms

Minimum Order Quantity: 300 meters

Packaging Details: Wooden drum, wood and steel drum,as customer's request

Delivery Time: 15 days

Payment Terms: L/C, T/T,

Get Best Price
High Light:

bare aluminum wire

,

bare electrical wire

Material:
AL
Out Sheath Color:
None
Core:
Normal Or Customized
Cable Drum Length:
Normal Or Customized
Characted:
Bare Conductor
Name:
AAC Conductor
Material:
AL
Out Sheath Color:
None
Core:
Normal Or Customized
Cable Drum Length:
Normal Or Customized
Characted:
Bare Conductor
Name:
AAC Conductor
Overhead Bare Conductor Wire(Nominal Area:400mm2), AAC Conductor Cable (AAC,AAAC,ACSR)

Overhead Bare Conductor Wire(Nominal Area:400mm2), AAC Conductor according to IEC 61089

 

AAC Conductor  APPLICATION

AAC conductor is also known as aluminium stranded conductor. It is manufactured from electrolytically refined aluminium, with a minimum purity of 99.7%.

 

AAC Conductor  STANDARD

Basic design to BS 215-1 / BS EN 50182 / IEC 61089 / ASTM B 231/B 231M / DIN 48201-5 standards.

 

Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

 

AAC Conductor  CONSTRUCTION

Concentric lay stranded Aluminium Conductor (AAC) is made up of one or more strands of hard drawn 1350 aluminum alloy. These conductors are used in low, medium and high voltage overhead lines. AAC has seen extensive use in urban areas where spans are usually short but high conductivity us required. The excellent corrosion resistance of aluminium has made AAC a conductor of choice in coastal areas. Because of its relatively poor strength to weight ratio, AAC had limited use in transmission lines and rural distribution because of long spans utilized. All aluminium conductors are made up of one or more strands of aluminium wire dep.

 

AAC Conductor TECHNICAL DATA

 

Numbers of Wires Final modules of Elasticity Coeficient of linear Expansion
AL Kg/mm2 Lb/in2 1/Cº 1/Fº
7 6000 8.5 x106 23.0 x10-6 112.8 x10-6
19 5700 8.1 x106 23.0 x10-6 112.8 x10-6
37 5700 8.1 x106 23.0 x10-6 112.8 x10-6
61 5500 7.8 x106 23.0 x10-6 112.8 x10-6
91 5500 7.8 x106 23.0 x10-6 112.8 x10-6

 

CONSTRUCTION PARAMETERS

• IEC 60189

Code Nominal Area Stranding Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
10 10 7/1.35 4.05 27.4 1.95 2.8633 62
16 16 7/1.71 5.13 43.8 3.04 1.7896 84
25 25 7/2.13 6.39 68.4 4.5 1.1453 110
40 40 7/2.70 8.1 109.4 6.8 0.7158 147
63 63 7/3.39 10.17 172.3 10.39 0.4545 195
100 100 19/2.59 12.95 274.8 17 0.2877 259
125 125 19/2.89 14.45 343.6 21.25 0.2302 297
160 160 19/3.27 16.35 439.8 26.4 0.1798 345
200 200 19/3.66 18.3 549.7 32 0.1439 396
250 250 19/4.09 20.45 687.1 40 0.1151 454
315 315 37/3.29 23.03 867.9 51.97 0.0916 522
400 400 37/3.71 25.97 1102 64 0.0721 603
450 450 37/3.94 27.58 1239.8 72 0.0641 647
500 500 37/4.15 29.05 1377.6 80 0.0577 688
560 560 37/4.39 30.73 1542.9 89.6 0.0515 736
630 630 61/3.63 32.67 1738.3 100.8 0.0458 789
710 710 61/3.85 34.65 1959.1 113.6 0.0407 845
800 800 61/4.09 36.81 2207.4 128 0.0361 905
900 900 61/4.33 38.97 2483.3 144 0.0321 967
1000 1000 61/4.57 41.13 2759.2 160 0.0289 1026
1120* 1120 91/3.96 43.56 3093.5 179.2 0.0258 1091
1250* 1250 91/4.18 45.98 3452.6 200 0.0231 1157
1400* 1400 91/4.43 48.73 3866.9 224 0.0207 1226
1500* 1500 91/4.58 50.38 4143.1 240 0.0193 1270

     

Overhead Bare Conductor Wire(Nominal Area:400mm2), AAC Conductor Cable (AAC,AAAC,ACSR) 0

     Why you choose us?

  • Registered capital of $30 million and factory covers an area of 60,000㎡;
  • Advanced test equipment and procedures, 100% inspection before factory;
  • Enough stocks and the higest efficient shipping time guarranteed;
  • Professional pre-sales and after-sales services provided.