Product Details
Place of Origin: Henan, China
Brand Name: Zhenglan Cable
Certification: CCC; ISO 9001:2015, ISO 14001:2005, CE
Model Number: ACSR Linnet
Payment & Shipping Terms
Minimum Order Quantity: 10ton
Price: Negotiable
Packaging Details: Wooden drum, Iron wood drum,as customer's request
Delivery Time: 15 days
Payment Terms: T/T, L/C
Supply Ability: 82,000 KM/Year
Name: |
ACSR Linnet 198.38SQMM |
Out Sheath Color: |
None |
Core: |
Steel |
Cable Drum Length: |
Wooden Or Iron Wooden Drum |
Characted: |
Bare Conductor |
Total Area: |
Al: 170.55mm²; Steel: 27.83mm² |
Application: |
Electrical Power Transmission |
Material: |
Aluminum And Steel |
Name: |
ACSR Linnet 198.38SQMM |
Out Sheath Color: |
None |
Core: |
Steel |
Cable Drum Length: |
Wooden Or Iron Wooden Drum |
Characted: |
Bare Conductor |
Total Area: |
Al: 170.55mm²; Steel: 27.83mm² |
Application: |
Electrical Power Transmission |
Material: |
Aluminum And Steel |
Aluminum Conductor Steel-Supported Core Bare Conductor Linnet 198.38SQMM
APPLICATION
ACSR conductors are widely used for electrical power transmission over long distances, since they are ideal for long overhead lines spans. They are also used as a messenger for supporting overhead electrical cables.
STANDARD
Basic design to BS 215-2 / BS EN 50182 / IEC 61089 / ASTM B 232/B 232M / DIN 48204 / JIS C 3110 standards
TECHNICAL DATA
Numbers of Wires | Modules of Elasticity | Coeficient of linear Expansion | |||
AL | STEEL | Kg/mm2 | Lb/in2 | 1/Cº | 1/Fº |
6 | 1 | 81 | 11.5 x106 | 19.1 x10-6 | 10.6 x10-6 |
6 | 7 | 77 | 11.0 x106 | 19.8 x10-6 | 11.0 x10-6 |
12 | 7 | 107 | 15.2 x106 | 15.3 x10-6 | 8.5 x10-6 |
18 | 1 | 67 | 9.5 x106 | 21.2 x10-6 | 11.8 x10-6 |
24 | 7 | 74 | 10.5 x106 | 19.6 x10-6 | 10.9 x10-6 |
26 | 7 | 77 | 10.9 x106 | 18.9 x10-6 | 10.5 x10-6 |
28 | 7 | 79 | 11.2 x106 | 18.4 x10-6 | 10.2 x10-6 |
30 | 7 | 82 | 11.6 x106 | 17.8 x10-6 | 9.9 x10-6 |
30 | 19 | 80 | 11.4 x106 | 18.0 x10-6 | 10.0 x10-6 |
32 | 19 | 82 | 11.7 x106 | 17.5 x10-6 | 9.7 x10-6 |
54 | 7 | 70 | 9.9 x106 | 19.3 x10-6 | 10.7 x10-6 |
54 | 19 | 68 | 9.7 x106 | 19.4 x10-6 | 10.8 x10-6 |
CONSTRUCTION PARAMETERS
• IEC 60189
Code | Nominal Area | Stranding | Overall Diameter | Weight | Breaking Load | Electrical Resistance @20° | Current Rating* | |||
AL | STEEL | TOTAL | AL | STEEL | ||||||
mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | Kg/Km | KN | Ω/Km | A | |
16 | 16 | 2.67 | 18.7 | 6/1.84 | 1/1.84 | 5.52 | 64.6 | 6.08 | 1.7934 | 85 |
25 | 25 | 4.17 | 29.2 | 6/2.30 | 1/2.30 | 6.9 | 100.9 | 9.13 | 1.1478 | 112 |
40 | 40 | 6.67 | 46.7 | 6/2.91 | 1/2.91 | 8.73 | 161.5 | 14.4 | 0.7174 | 150 |
63 | 63 | 10.5 | 73.5 | 6/3.66 | 1/3.66 | 10.98 | 254.4 | 21.63 | 0.4555 | 198 |
100 | 100 | 16.7 | 117 | 6/4.61 | 1/4.61 | 13.83 | 403.8 | 34.33 | 0.2869 | 263 |
125 | 125 | 6.94 | 132 | 18/2.97 | 1/2.97 | 14.85 | 397.9 | 29.17 | 0.2304 | 299 |
125 | 125 | 20.4 | 145 | 26/2.47 | 7/1.92 | 15.64 | 503.9 | 45.69 | 0.231 | 302 |
160 | 160 | 8.89 | 169 | 18/3.36 | 1/3.36 | 16.8 | 509.3 | 36.18 | 0.18 | 347 |
160 | 160 | 26.1 | 186 | 26/2.80 | 7/2.18 | 17.74 | 644.9 | 57.69 | 0.1805 | 351 |
200 | 200 | 11.1 | 211 | 18/3.76 | 1/3.76 | 18.8 | 636.7 | 44.22 | 0.144 | 398 |
200 | 200 | 32.6 | 233 | 26/3.13 | 7/2.43 | 19.81 | 806.2 | 70.13 | 0.1444 | 402 |
250 | 250 | 24.6 | 275 | 22/3.80 | 7/2.11 | 21.53 | 880.6 | 68.72 | 0.1154 | 458 |
250 | 250 | 40.7 | 291 | 26/3.50 | 7/2.72 | 22.16 | 1007.7 | 87.67 | 0.1155 | 461 |
315 | 315 | 21.8 | 337 | 45/2.99 | 7/1.99 | 23.91 | 1039.6 | 79.03 | 0.0917 | 526 |
315 | 315 | 51.3 | 366 | 26/3.93 | 7/3.05 | 24.87 | 1269.7 | 106.83 | 0.0917 | 530 |
400 | 400 | 27.7 | 428 | 45/3.36 | 7/2.24 | 26.88 | 1320.1 | 98.36 | 0.0722 | 607 |
400 | 400 | 51.9 | 452 | 54/3.07 | 7/3.07 | 27.63 | 1510.3 | 123.04 | 0.0723 | 610 |
450 | 450 | 31.1 | 481 | 45/3.57 | 7/2.38 | 28.56 | 1485.2 | 107.47 | 0.0642 | 651 |
450 | 450 | 58.3 | 508 | 54/3.26 | 7/3.26 | 29.34 | 1699.1 | 138.42 | 0.0643 | 655 |
500 | 500 | 34.6 | 535 | 45/3.76 | 7/2.51 | 30.09 | 1650.2 | 119.41 | 0.0578 | 693 |
500 | 500 | 64.8 | 565 | 54/3.43 | 7/3.43 | 30.87 | 1887.9 | 153.8 | 0.0578 | 697 |
560 | 560 | 38.7 | 599 | 45/3.98 | 7/2.65 | 31.83 | 1848.2 | 133.74 | 0.0516 | 741 |
560* | 560 | 70.9 | 631 | 54/3.63 | 19/2.18 | 32.68 | 2103.4 | 172.59 | 0.0516 | 745 |
630 | 630 | 43.6 | 674 | 45/4.22 | 7/2.81 | 33.75 | 2079.2 | 150.45 | 0.0459 | 794 |
630* | 630 | 79.8 | 710 | 54/3.85 | 19/2.31 | 34.65 | 2366.3 | 191.77 | 0.0459 | 798 |
710 | 710 | 49.1 | 759 | 45/4.48 | 7/2.99 | 35.85 | 2343.2 | 169.56 | 0.0407 | 851 |
710* | 710 | 89.9 | 800 | 54/4.09 | 19/2.45 | 36.79 | 2666.8 | 216.12 | 0.0407 | 856 |
800* | 800 | 34.6 | 835 | 72/3.76 | 7/2.51 | 37.61 | 2480.2 | 167.41 | 0.0361 | 910 |
800* | 800 | 66.7 | 867 | 84/3.48 | 7/3.48 | 38.28 | 2732.7 | 205.33 | 0.0362 | 912 |
800* | 800 | 101 | 901 | 54/4.34 | 19/2.61 | 39.09 | 3004.9 | 243.52 | 0.0362 | 916 |
900* | 900 | 38.9 | 939 | 72/3.99 | 7/2.66 | 39.9 | 2790.2 | 188.33 | 0.0321 | 972 |
900* | 900 | 75 | 975 | 84/3.69 | 7/3.69 | 40.59 | 3074.2 | 226.5 | 0.0322 | 974 |
1000* | 1000 | 43.2 | 1043 | 72/4.21 | 7/2.80 | 42.08 | 3100.3 | 209.26 | 0.0289 | 1031 |
1120* | 1120 | 47.3 | 1167 | 72/4.45 | 19/1.78 | 44.5 | 3464.9 | 234.53 | 0.0258 | 1096 |
1120* | 1120 | 91.2 | 1211 | 84/4.12 | 19/2.47 | 45.31 | 3811.5 | 283.17 | 0.0258 | 1100 |
1250* | 1250 | 102 | 1352 | 84/4.35 | 19/2.61 | 47.85 | 4253.9 | 316.04 | 0.0232 | 1165 |
1250* | 1250 | 52.8 | 1303 | 72/4.70 | 19/1.88 | 47 | 3867.1 | 261.75 | 0.0231 | 1163 |
1120* | 1120 | 91.2 | 1211 | 84/4.12 | 19/2.47 | 45.31 | 3811.5 | 283.17 | 0.0258 | 1100 |
CONSTRUCTION
ACSR 120/20 conductors are formed by several wires of aluminium and galvanized steel, stranded in concentric layers. The wire or wires which form the core, are made of galvanized steel and the external layer or layers, are of aluminium. Galvanized steel core consist normally of 1, 7 or 19 wires. The diameters of steel and aluminium wires can be the same, or different.
By varying the relative proportions of aluminium and steel, the required characteristics for any particular application can be reached. A higher U. T. S. Can be obtained, by increasing steel content, and a higher current carrying capacity by increasing aluminium content.
Why you choose us?