Product Details
Place of Origin: Henan, China
Brand Name: Zhenglan cable
Certification: 3C; ISO 9001:2015, ISO 14001:2005, OHSAS 18001:2007
Model Number: MEDIMUM VOLTAGE POWER CABLE ARMORED POWER CABLE 3CORE 70MM2 8.7/15KVKV
Payment & Shipping Terms
Minimum Order Quantity: 300 meters
Price: 1-200USD/m
Packaging Details: Wooden drum, wood and steel drum,as customer's request
Delivery Time: 12 days
Payment Terms: L/C,T/T,
Supply Ability: 50000m/day
Outer Sheath Material: |
PVC |
Conductor: |
Copper |
Sheath: |
PVC |
Insulation: |
XLPE(TR-XLPE Optional) |
Ambient Temperature: |
Fixed: -40°C To +80°C, Flexed: +5°C To +80°C |
Standards: |
IEC 60502-2 |
Outer Sheath Material: |
PVC |
Conductor: |
Copper |
Sheath: |
PVC |
Insulation: |
XLPE(TR-XLPE Optional) |
Ambient Temperature: |
Fixed: -40°C To +80°C, Flexed: +5°C To +80°C |
Standards: |
IEC 60502-2 |
Application:
It is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable.
Features:
1. Rated voltage: Uo/U: 26/35kV, 21/35kV, 12/20 kV (24 kV), 8.7/10kV, 8.7/15kV, 6/6kV, 6/10kV.
2. No. of core: Single-core, Three-core.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. Long-term is no more than 5 seconds). The highest temperature for conductor is no more than 250.
4. D.C Resistance of the conductor complies with the stipulations of GB/T3956-1997.
5. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
6. The cable is laid without horizontal drop limit. The Min. Bending radius of three-core cable should be no smaller than 12 times of cable outer diameter.
7. Working Frequency Voltage Test:.
For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture.
For cable with Uo of 3.6kv~18kV: 3.5Uo/5min without puncture.
For cable with Uo of 21kV and 26 kV: 2.5Uo/30min without puncture.
Technical Parameters:
Nominal cross sectional area of conductor(mm²) | lnsulation thickness (mm) | Sheath thickness (mm) | Approx. overall diameter of cable(mm) | Approx.weight Of cable (kg/km) | D.C resistance of conductor(Ω/km) | Testing voltage A.C | Current rating | |||||
In air(A) | Direct in soil(A) | |||||||||||
Cu | AI | Cul | Al | (kV/5min) | Cu | Al | Cu | Al | ||||
3 x70 | 4.5 | 2.8 | 55 | 4197 | 2895 | ≤0.268 | ≤0.443 | 30.5 | 220 | 170 | 220 | 170 |