Send Message
Zhenglan Cable Technology Co., Ltd
products
products
Home > products > Twin And Earth Cable > High Temperature RV Twin And Earth Cable ISO 9001:2015 Certificated/(450/750) PVC insulated cables

High Temperature RV Twin And Earth Cable ISO 9001:2015 Certificated/(450/750) PVC insulated cables

Product Details

Place of Origin: China

Brand Name: Zhenglan cable

Certification: 3C,ISO 9001:2015,ISO 14001:2005

Model Number: RV Cable(450/750) PVC insulated cables

Payment & Shipping Terms

Minimum Order Quantity: 100 meters

Packaging Details: Rolls

Delivery Time: 5~10 days

Payment Terms: L/C, T/T,

Get Best Price
High Light:

multi strand electrical wire

,

two core and earth cable

Material:
99.99% Oxygen Free Copper
Type:
PVC Insulated
Application:
For Home Use
Voltage:
450/750V
Nominal Section Area:
1.5~70mm²
Material:
99.99% Oxygen Free Copper
Type:
PVC Insulated
Application:
For Home Use
Voltage:
450/750V
Nominal Section Area:
1.5~70mm²
High Temperature RV Twin And Earth Cable ISO 9001:2015 Certificated/(450/750) PVC insulated cables

High Temperature RV Twin And Earth Cable ISO 9001:2015 ISO 14001:2005 Certificated/(450/750) PVC insulated cables

 

Twin And Earth Cable Application:

RV cable is widely used in industrial distribution field. It is especially suitable for flexible installation places with stricter requirements, such as electronic control cabinets, distribution boxes and various low-voltage electrical equipment. It can be used for transmission of power, electrical control signals and switching signals. RV wire and cable are designed with soft structure. The bending radius of conductor is small, and it is suitable for wet and oily installation places.

 

Twin And Earth Cable Construction characteristics

Conductor: flexible conductor class 5 (China GB/T 3956 class 5 or

IEC60228 class 5)

Insulation: PVC

Rated voltage and standard:

300/500V 60227 IEC06 or GB/T5023.3-2008

450/750V 60227 IEC02 or GB/T5023.3-2008

Minimum service temperature: - 30 C

Maximum service temperature available +70 °C, +90 °C, +105 °C

Packaging: 100m/roll or as request

 

Remarks: Flame retardant, fire resistance (adopt mica tape), low smoking and Halogen free, or other property are available.

ZR cable (flame retardant cable) is the kind of cable with PVC insulation built mixed with fire prevention additive to make it have the capability of preventing or retarding flame spread during combustion.

There are 3 grades of fire prevention available which are

Grade A It is the highest level of flame retardancy. That is, the insulation material, filling rope, fastening (inner cushion) belt/layer and sheath material used in cables are all flame retardant materials.

Grade B Except the insulation material, all other materials are flame retardant.

Grade C Only the sheath material is flame retardant

NH cable (fire resistant cable) is the kind of cable built with a layer of mica tape. Even if the plastic skin is burnt out, refractory layer will help not cause short circuit. When wiring, cut off the refractory layer at the wire head.

LSZH,LSOH,LS0H,LSFH or OHLS cable(Low smoke zero halogen cable)is cable with insulation or outer sheath built using low smoke zero halogen free material to help reduce toxic and corrosive gases produced during combustion.

Termite-proof cable is the cable built with insulation or outer sheath mixed with a kind of materials to prevent termite biting the cable.

 

Twin And Earth Cable Data sheet

 

300/500V

Nominal section area(mm²) No ./Dia.
of
Strand
(mm)
Nom.
Thickness
of insulation
(mm)
Average
OD Max.
(mm)
Max. DC conductor
resistance at 20℃
(Ω/km)
Min. Insulating
resistance
at 70℃
(MΩ·km)
1*0.5 16/0.2 0.6 2.6 9.1 0.013
1*0.75 24/0.2 0.6 2.8 12.2 0.011
1*1.0 32/0.2 0.6 3.0 15.1 0.010

RV-90℃

Nominal section area(mm²) Core no./dia(mm)

Max diameter

(mm)

Insulation thickness

(mm)

Reference weight

(kg/km)

90℃Minimum insulation electric resistance(mΩ/km)
1*0.5 16/0.2 2.5 0.6 10.2 0.013
1*0.75 24/0.2 2.7 0.6 13.5 0.012
1*1.0 32/0.2 2.8 0.6 16.4 0.010
1*1.5 30/0.25 3.4 0.7 21.4 0.009
1*2.5 49/0.25 4.1 0.8 34.5 0.009

 

450/750V

Nominal section area(mm²) No ./Dia.
of
Strand
mm
Nom.
Thickness
of insulation
mm
Average
OD (Max.)
mm
Max. DC conductor
resistance at 20℃
Ω/km
Min. Insulating
resistance
at 70℃
MΩ·km
1*1.5 30/0.25 0.7 3.5 13.3 0.010
1*2.5 50/0.25 0.8 4.2 7.98 0.009
1*4 77/0.26 0.8 4.8 4.95 0.007
1*6 78/0.31 0.8 6.3 3.30 0.006
1*10 84/0.39 1.0 7.6 1.91 0.0056
1*16 133/0.39 1.0 8.8 1.21 0.0046
1*25 189/0.41 1.2 11.0 0.78 0.0044
1*35 259/0.41 1.2 12.5 0.554 0.0038
1*50 361/0.41 1.4 14.5 0.386 0.0037
1*70 337/0.51 1.4 17.0 0.272 0.0032